Site Transformer, 230:110V, 10 kVA single-phase, continuously rated, 2 x 32A and 4 x 16A sockets, also incorporating 2 x 16A DP MCBs for direct connection to lighting circuits (3 Core).
Construction Site Transformers
Site Power & Lighting Transformer with MCB Protection
Type Ref: TA/P/1/10/S6/C2-16
£803.25
Can’t find what you’re looking for?
We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!
Site Power and Lighting Transformer, 10 kVA single-phase, manufactured in accordance with the requirements of BS4363.
Enclosure
Robust, free-standing, non-vented, sheet steel enclosure of welded construction, incorporating certified lifting handles. The enclosure provides protection to IP44 and has a durable, oven dried polyester powder coated finish, shade Traffic Yellow.
Rating
10 kVA single-phase, continuously rated
Primary Volts
230
Primary Protection
50A DP Type “D” MCB
Secondary Volts
110CTE providing a Reduced Low Voltage (RLV) supply
Distribution
2 no. 32A 2P+E 110V IP44 sockets each protected by 1 no. 32A DP Type “C” MCB, 4 no. 16A 2P+E 110V IP44 sockets protected by 2 no. 16A DP Type “C” MCBs and 2 no. 16A DP MCB feeding 3 way terminal blocks for direct connection to lighting circuits (the lighting connections can be made without removing the transformer lid).