Sensor Based RCDs

SRC Series Steel RCD / Overcurrent Protection Assembly

Type Ref: SRC/OC/4/MRCD800

800A icon IP54 icon Steel icon Variable RCD icon

£5332.5

Can’t find what you’re looking for?

We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!

SRC series Steel RCD / Overcurrent Protection Assembly, 800A, 4P, Variable RCD, IP54

SRC series of high current Modular Residual Current Device (MRCD) configured for bottom cable entry and exit. Assembly provides Type A RCD protection in accordance with BS EN 60947-2 (annex M), as required by BS7671:2018 (18th Edition IET Wiring Regulations). The assembly also incorporates over current and short-circuit protection.

Enclosure
Wall mounting sheet steel enclosure of seam welded construction providing protection to IP54. The enclosure incorporates a projecting rain roof, side hinged door and removable gland plate. It is protected against corrosion by a high quality, outdoor duty finishing system comprising of a zinc phosphate pre-treatment followed by polyester powder coating, colour bright red (Vermilion, RAL 2002).
Enclosure dimensions: 1055H x 980W x 332D mm.

MCCB
Fitted with an 800A 4P MCCB with switched neutral. The MCCB is adjustable from 800A to 320A and is fitted with a shunt-trip.

RCD
The assembly incorporates a Blakley Electrics MRCD-R series earth leakage sensor with sensitivity adjustable from 0.1A to 30A and time delay adjustable from 0 to 10 seconds. The sensor operates the shunt-trip incorporated within the associated MCCB.

Terminations
The incoming supply terminates directly on to the MCCB, which is shrouded to IP2X. The load cables terminate on to heavy duty stud type terminals (the sensor CT is pre-wired in flexible cable).

Product Downloads

Data Sheets

Drawings

On Application

This product cannot currently be purchased online. Please contact Blakley Electrics Customer Services on 0333 188 0284 to discuss your requirements and for pricing and lead times.