Standard Industrial Transformers

TDC Series Transformer Distribution Cubicle

Type Ref: TDC/2/RCD-300/C4-16/WM

2kVA icon Continuous rating icon Wall mounting icon RCD icon IP23 icon

P.O.A

Can’t find what you’re looking for?

We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!

TDC series Transformer Distribution Cubicle, Wall Mounting, 2 kVA, 230:110CTE, 4 x 16A MCBs. The transformer output is also protected by a 300mA 110V RCCB to ensure compliance with BS7671 Regulation 411.8.3.

Blakley Electrics TDC series of Transformer Distribution Cubicle combining a double-wound transformer and double-pole MCB distribution arrangement housed in a robust sheet steel enclosure. The assembly provides a Reduced Low Voltage (RLV) supply in accordance with BS7671.

Enclosure
Wall mounting, sheet steel, seam welded enclosure, phosphate pre-treated prior to powder coating, shade Traffic Yellow. The transformer compartment is ventilated to IP23. The MCB compartment is non-vented and has a padlockable, side-hinged, gasketted door. Cable entry and exit is via a removable gland plate located in the underside of the enclosure.
Dimensions: 330 x 210 x 540 mm (W x D x H).

Rating
2000 VA single-phase, double-wound, continuously rated transformer, manufactured in accordance with BS EN 61558 Parts 1 & 2-4 with an earthed secondary winding.

Primary Isolator
Fitted a 10A DP MCB, Type “D”.

Primary Volts
230 with tappings at 220, 240 and 250 volts.

Secondary Volts
110 CTE (in accordance with BS EN 61558 Part 2-23).

RCD Protection
The transformer output is protected by a 300mA 110V Type A RCCB to ensure compliance with BS7671 Regulation 411.8.3, which specifies a 5 second disconnection time for RLV circuits.

Distribution
Fitted 4 no. 16A DP MCBs to BS EN 60898 Type “C”.

Product Downloads

Data Sheets

Drawings