TLW series Transformer Assembly with primary isolator, 2 kVA continuously rated (3300VA intermittent rating), 230:110CTE, 2 x 16A 110V sockets with integral DP MCB protection. Switchgear protected by a hinged window.
Standard Industrial Transformers
TLW Series Transformer Assembly
Type Ref: TLW/I/2/C1/S2/IP44
£517.37
Can’t find what you’re looking for?
We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!
Blakley Electrics enclosed transformer assembly providing a Reduced Low Voltage Supply (RLV) in accordance with BS7671 (IEE Wiring Regulations). The assembly is supplied complete with the fitments detailed below:
Enclosure
TL series, wall mounting, sheet steel, non-vented to IP44. The enclosure is phosphate pre-treated prior to electrostatically applied powder coating, shade Dark Admiralty Grey.
The wall mounting brackets can be repositioned on-site to make the enclosure floor fixing.
Rating
2000 VA single-phase continuously rated or 3300VA intermittently rated. The transformer is double wound and manufactured in accordance with BS EN 61558 Parts 1 and 2-4.
Primary Switch
Fitted with a 20A SP switch disconnector.
Primary Volts
230 with tappings at 220, 240 and 250 volts.
Secondary Volts
110 CTE (in accordance with BS EN 61558 Part 2-23).
Distribution
2 no. 16A, 2P+E, 110V, IPX4, BS EN 60309-2 sockets protected by 1 no. 16A DP Type “C” MCB.
The MCB and switch are located behind a hinged window to maintain the IP rating.