Changeover Assemblies

500A Generator Connection Point

Type Ref: GCP/500

500A icon IP55 icon

P.O.A

Can’t find what you’re looking for?

We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!

Generator Connection Point comprising of a wall mounting enclosure housing a set of single pole 500A drain power connectors with controlled access (for a temporary generator connection) and a segregated termination chamber for the permanent mains outgoing connection.

Please note: the largest cable that can be terminated in a cable mounted single pole connector is 300mm².

Generator Connection Point comprising of a wall mounting enclosure housing a set of single pole 500A drain power connectors with controlled access to the powerlocks, which provides greater security against accidental or unauthorised withdrawal or insertion of connectors. A segregated termination chamber for the permanent mains outgoing connection is incorporated.

Enclosure
Wall mounting enclosure of seam welded construction, fabricated from mild steel, protected against corrosion by a high quality, outdoor finish comprising of a zinc phosphate pre-treatment followed by electrostatically applied and oven dried polyester powder paint, shade Dark Admiralty Grey (BS 4800 shade 18B25).
Enclosure dimensions: 965 x 668 x 248mm (H x W x D).

General arrangement
The upper outgoing termination chamber is protected to IP55 and houses a set of 5 no. 500A copper connection bars and has a removable rear access plate for the outgoing permanent cables. The bars are fitted with M12 stud terminals. The chamber is fitted with a top removable gland plate but this can be replaced by a projecting canopy.
The lower chamber is provided with a side hinged, padlockable door and is fitted with 5 no. 500A drain SP connectors (which are connected to the upper termination chamber). The lower chamber has an open “letterbox” slot in the underside for cable entry. The door can be closed with 5 no. single core cables fitted with SP source connectors inserted into the drains.

Please note: the largest cable that can be terminated in a cable mounted single pole connector is 300mm².

Options to be specified at time of ordering (subject to additional cost)
Sequential Powerlocks where connectors must be connected / disconnected in sequence (earth is first in and last out).
Stainless steel enclosure (grade of stainless steel to be specified).

Product Downloads

Data Sheets

Drawings

On Application

This product cannot currently be purchased online. Please contact Blakley Electrics Customer Services on 0333 188 0284 to discuss your requirements and for pricing and lead times.