Site Lighting Transformer, 400:110V, 10 kVA three-phase, continuously rated, 6 x 16A DP MCBs for direct connection to lighting circuits.
Construction Site Transformers
Site Lighting Transformer with MCB Protection
Type Ref: TA/P/3/10/C6-16
£876.75
Can’t find what you’re looking for?
We’re always here to help! Give us a call or fill out our contact form and a member of our team will be in touch!
Site Lighting Transformer, 10 kVA three-phase, manufactured in accordance with the requirements of BS4363.
Enclosure
Robust, free-standing, non-vented, sheet steel enclosure of welded construction, incorporating certified lifting handles. The enclosure provides protection to IP44 and has a durable, oven dried polyester powder coated finish, shade Traffic Yellow.
Rating
10 kVA three-phase, continuously rated
Primary Volts
400 Delta Connection
Primary Protection
16A TP Type “D” MCB
Secondary Volts
110NE providing a Reduced Low Voltage (RLV) supply
Distribution
6 no. 16A DP MCBs feeding 3 way terminal blocks for direct connection to lighting circuits (the lighting connections can be made without removing the transformer lid).